Dräger Flame 1500 (IR3)
Dräger Flame 1500 (IR3)
Images and Videos
Downloads

Flame 1500 Product Information, en_us
Technical Data
Key Facts
- Field of view
- Horizontal 90°; Vertical 90°
- Response time
- Typically 4 seconds
- Cable entry
- Dual M25 or ¾''NPT
- Detection Technology
- IR3
- Flameproof
- ✓
- Increased Safety
- ✗
- SIL
- ✓ (SIL 2)
- 4-20 mA
- ✓
- HART®
- ✓
- RS-485
- ✓
- Relay
- ✓
Fuel ft / m
- n-Heptane / Gasoline
- 200 / 60
- Diesel Fuel / JP5 / Kerosene
- 165 / 50
- Ethanol 95 %
- 136 / 42
- Methanol
- 136 / 42
- IPA (Isopropyl Alcohol)
- Hydrogen
- Methane
- 165 / 50
- LPG
- Polypropylene Pellets
- Ammonia
- Silane
- Office Paper
Technical Data
- Power Supply
- 24 V DC
- Temperature (operation)
- -60°C - 85°C
- Humidity
- 0 to 100 % r.h., non-condensing
- Dimensions (H × W × D)
- 0.22x0.1 m
- Weight
- 13.23 lb
- Housing Material
- Aluminium or stainless steel, powder-coated
- Degree of protection (IP class)
- IP66
Approvals
- ATEX
- ✓
- IECEx
- ✓
- UL
- ✗
- CSA
- ✗
- CE marking
- ✓
- GOST (EAC)
- ✗
- Performance approval
- ✓
- Shipping approval (DNV & MED)
- ✓