Dräger Polytron 2000
Contact usDräger Polytron 2000
Toxic Gases and Oxygen Detector
- Sensor: Electrochemical Sensor
- Installation: non-explosion proof
- Interface: 4-20 mA
- IP class: IP 54
- Special: display
Robust, precise, safe
The globally proven Dräger sensor technology
forms the core of the Polytron 2000.
The miniaturised electrochemical sensor
(MEC) stands out for its longevity and
precision. The DrägerSensor MEC marks
the introduction of a new design for
electrochemical sensors into the stationary
gas detectors made by Dräger, which are
matched precisely to the basic applications
of stationary gas transmitters.
The Polytron 2000 has protection class
IP54 dust and water protection and
a robust polyamide housing. But the internals
of the device are also extremely
robust. The transmitter electronics of the
Polytron 2000 are designed for temperatures
of - 40° to + 65 °C and are thus highly
suitable for the most diverse operating
conditions.
Simple and energy-saving
The modular concept of docking station and transmitter can be assembled in no time at all. The docking station can be pre-installed and cabled, thus saving time. Commissioning is carried out by simply inserting the transmitter in the docking station and locking it by means of a quick-release fastener. The low energy consumption of just 50 mW permits a simple 2-wire installation.
Immediately ready for use
The Polytron 2000 is pre-configured to the required gas and measuring range before use. The device is thus immediately ready for use and no longer has to be adjusted. This also applies to the Dräger MEC sensor. It is equipped with an internal datalogger and is pre-calibrated accordingly. The Polytron 2000 is thus operational immediately after a warm-up phase.
Easy diagnosis and maintenance
All measurement, warning and maintenance values as well as fault states are shown on the display and can simply be read off. Maintenance of the Polytron 2000 is quick and easy to carry out.
Images and Videos
Downloads

Polytron 2000 Product Information, en
Robust, precise, safe – the Dräger Polytron® 2000 is a stationary gas detector for measuring standard gases (O2, H2S, NH3, Cl2, CO). With the new, pre-calibrated DrägerSensor MEC and robust design, this gas transmitter is a reliable and economic solution for non-explosion proof areas.

IfU Polytron 2000 9033358 me
These instructions for use are provided for informational purposes only. Please always read and comply with the instructions for use delivered with the product.
Sensors and substances
Dräger Sensors for fixed gas detectors can be used to measure a large number of hazardous substances. Check the different sensors by searching for a substance. Get in contact with our experts to get more information.
Product configurations
Utilize for 12 Substances
8 matching SensorFGDS
Technical Data
Key Facts
- Type
- Transmitter
- Cable entry
- M20 x 1.5
- Display
- ✓
- Intrinsic Safety
- ✗
- Flameproof
- ✗
- Increased Safety
- ✗
- SIL
- ✗
- 4-20 mA
- ✓
- Bus
- ✗
- HART®
- ✗
- Wireless
- ✗
Technical Data
- Power Supply
- 12 to 30 V DC, 2-wire
- Temperature (operation)
- -40°C - 65°C
- Humidity
- 0 to 100% r.h., non-condensing
- Pressure (hPa)
- 700 - 1300
- Dimensions (H × W × D)
- 0.17x0.14x0.12 m
- Weight
- 0.9 Kg
- Housing Material
- Glass fibre reinforced polyester (GFRP)
- Degree of protection (IP class)
- IP54
Approvals
- ATEX
- ✗
- IECEx
- ✗
- UL
- ✗
- CSA
- ✗
- CE marking
- ✓
- GOST (EAC)
- ✗
- Performance approval
- ✗
- Shipping approval (MED)
- ✗