Dräger Polytron® SE Ex
Contact usDräger Polytron® SE Ex
Flammable Gas Detectors
- Sensor: Catalytic bead sensor
- Installation: Increased Safety
- Interface: 3-wire cable
- IP class: IP 66
- Special: Sensing Head
Heat of reaction principle
By the heat of reaction principle, concentrations of flammable gases can be detected long before they tend to be ignitable, in other words: before they reach the lower explosive limit (LEL). The sensing heads are intended to be used in the harsh industrial environment and connected to a suitable central controller by means of a 3-core cable. Based on different sensor types Dräger offers three versions for different applications: On the one hand for the detection of up to 100 % LEL (where a special HT-version can be used at ambient temperatures up to 150 °C), on the other hand for the detection of very low concentrations in the range 0 ... 10 % LEL (leak detection).
Six housing variants
The sensing heads Dräger Polytron SE Ex PR ... DQ and SE Ex LC ... DD are available as four variants each, which differ by their junction boxes, specified by the following code:
M1 - small standard housing
M2 - midsize standard housing
Besides these junction boxes made of glass fiber reinforced Polyester (GRP) with type of protection “e” (increased safety) housing a sensor with metric (“M”) thread, a further variant with type of protection “d” (flameproof enclosure) is available, coded as:
NPT1 - flame-proof metal housing
This variant houses a sensor with NPT-thread and is intended to be used in conduit installations. The variant M2 should preferably be used in outdoor applications since the lateral cable gland may be exchanged by the stopping plug so that the cable can be inserted from the bottom.
Comprehensive explosion protection
The sensing heads Polytron SE Ex ... DQ are labeled according to the Directive 2014/34/EU as II 2G/ II 2D and thus are suitable for operation in areas with potentially explosive atmospheres of zone 1 and 2 as well as zone 21 and 22. In the same way, for world-wide applications, an IECEx-approval allows to operate these sensing heads in hazardous areas.
mV measuring signal
The flame-proof encapsulated gas sensor produces a mV-signal which is proportional to the gas concentration and can be evaluated by a suitable central controller (e.g. Dräger REGARD or Polytron SE Ex). Connected to the sensing head via a shielded 3-core cable of several hundreds of meters length, the central controller is intended to activate alarms if dangerous gas concentrations occur.
Pellistor sensors type DQ
Since they are operated as precisely measuring temperature dependent resistors, the measuring beads housed in the sensor are called pellistors (from engl. pellet and resistor). A pellistor is a small bead made of very porous ceramic material which is impregnated by a special catalyst and embedding a small platinum filament. By means of an electrical current of approx. 255 mA on the one hand the platinum filament heatsup the ceramic bead to roughly 450 °C,on the other hand this platinum wire actsas a measuring resistor dependent on thebead’s temperature. When molecules of a flammable gaspenetrate into the catalytic bead they reactwith the activated airborne oxygen which is adsorbed in the porous ceramic and release heat of reaction causing the pellistor’s temperature rising. The resulting resistance increase of some milli-Ohms is proportional to the gas concentration.
Compensation of environmental conditions
By means of a second, entirely uniform pellistor, which is especially encapsulated, any parameter affecting precise measurement is optimal compensated. This is particularly true in respect to humidity and ambient temperature. During manufacturing these pellistors are matched in respect to optimum compensation characteristics. Since both these pellistors are catalytic the sensor is called type DQ (double detector) with a resulting long-term stable sensor signal being nearly unaffected by ambient temperature changes.
Poison resistance
The pellistors which are manufactured since decades are of type PR, which means poison resistant. Based on their special construction these sensors have a longer lifetime compared to conventional sensors when being exposed to industrial atmospheres containing catalyst poisons such as sulfur-, phosphor-, lead- or siliconcompounds.
Very short response times
To achieve short response times the gas entrance of the DQ-sensor is not a conventional sinter disc but a thin wire mesh disc so that the gas to be detected can very quickly enter the pellistors by way of diffusion.
Measuring function for explosion protection
In conjunction with some Dräger central controller units the Dräger sensing heads Polytron SE Ex PR ... DQ and HT M DQ are type-approved to be used in pre ventive explosion protection applications acc. to EN 1127-1. This is a customer’s benefit since in case of a dangerous gas concentration a performance approved gas detection system will auto matically activate countermeasures so that explosive concentrations cannot form and the extension of hazardous areas thus decrease. By this, electrical installations can be designed more simply and in some cases even no further explosion protection measures are necessary. This is because potentially explosive atmospheres occur seldom or even not at all when having a gas detection system like this.
Images and Videos
Downloads

Polytron SE Ex Product Information, en
The Dräger Polytron® SE Ex ... DQ sensing heads are gas detectorsfor the continuous monitoring of flammable gases and vapours in theambient air. Measurement is based on the heat of reaction principlewhere a chemical reaction takes place in a catalytic bead (also known as apellistor) inside the sensor.

SIL Brochure, en
Safety Instrumented Systems are used to reduce the risk for the protection of people, plants, and environment.

IFU Polytron SE Ex - 9033888 de-me
These instructions for use are provided for informational purposes only. Please always read and comply with the instructions for use delivered with the product.
Sensors and substances
Dräger Sensors for fixed gas detectors can be used to measure a large number of hazardous substances. Check the different sensors by searching for a substance. Get in contact with our experts to get more information.
Product configurations
Utilize for 29 Substances
5 matching SensorFGDS
Technical Data
Key Facts
- Type
- Sensing head
- Response time
- Cable entry
- M20 x 1.5
- Display
- ✗
- Intrinsic Safety
- ✗
- Flameproof
- ✓
- Increased Safety
- ✓
- SIL
- ✓ (SIL 1)
- 4-20 mA
- ✗
- Bus
- ✗
- HART®
- ✗
- Wireless
- ✗
Technical Data
- Power Supply
- Temperature (operation)
- -50°C - 85°C
- Humidity
- 5 to 95 % r.h., non-condensing
- Pressure (hPa)
- 800 - 1100
- Dimensions (H × W × D)
- 0.14x0.11x0.06 m
- Weight
- 0.6 Kg
- Housing Material
- Glass fiber reinfrorced polyester (GFRP) or aluminum
- Degree of protection (IP class)
- IP66
Approvals
- ATEX
- ✓
- IECEx
- ✓
- UL
- ✗
- CSA
- ✗
- CE marking
- ✓
- GOST (EAC)
- ✗
- Performance approval
- ✓
- Shipping approval
- ✓
- FM
- ✗