Dräger Flame 2000 (IR)

With its highly sensitive IR sensor the Dräger Flame 2000 detects hydrocarbon-based fires. It offers high reliability against false alarms.

Fast and reliable detection

The Flame 2000 works with a highly sensitive IR-sensor in a wavelength range of 4.5 µm. This enables very fast detection of hydrocarbon-based fires. This degree of reliability complies with the IEC 61508 safety integrity requirements of SIL2.
Moreover, the flame detector has HART® and RS-485 Modbus interfaces and requires very little power.

Prevention of false alarms

The Flame 2000 is immune to sources of interference. This prevents false alarms. Frequent error sources such as sunlight or other IR sources no longer present a problem. Moreover, the sensitive detection ensures that the detector does not falsely set off an alarm for fires emanating from other areas.

Robust and resistant

The housing is very resilient and weatherproof. The viewing window is heated to protect it from icing and fogging up. This allows you to operate the Flame 2000 reliably under the most diverse environmental conditions.

Simple check

The Built-in-Test (BIT) automatically checks the electronics and the optics of the Flame 2000. You can also perform the check manually. A tri-coloured LED at the front of the detector provides a quick status indication. Green indicates normal operation, yellow indicates a fault and red indicates a fire alarm.

Downloads

Flame 2000 (IR)  Product Information, en
Flame 2000 (IR) Product Information, en

With its highly sensitive IR sensor the Dräger Flame 2000 detects hydrocarbon-based fires. It offers high reliability against false alarms.

Download

More than the sum Brochure, en
More than the sum Brochure, en

Dräger is a successful global player in the field of stationary gas measuring technology since more than 70 years. We have been developing gas measuring products, setting new standards for measuring accuracy, durability and customer-specific adaptation.

Download

Dräger Flame 2xx0 Host Software VC
Dräger Flame 2xx0 Host Software VC

Download

Technical Data

Key Facts

Field of view
Horizontal 90°; Vertical 90°
Response time
Typically 5 seconds
Cable entry
2 × 3/4" – 14NPT or 2 × M25 × 1.5 mm
Detection Technology
IR
Flameproof
Increased Safety
SIL
✓ (SIL 2)
4-20 mA
HART®
RS-485
Relay

Fuel ft / m

n-Heptane / Gasoline
50 / 15
Diesel Fuel / JP5 / Kerosene
37 / 11
Ethanol 95 %
25 / 7.5
Methanol
25 / 7.5
IPA (Isopropyl Alcohol)
25 / 7.5
Hydrogen
Methane
29.5 / 9
LPG
29,5 / 9
Polypropylene Pellets
37 / 11
Ammonia
Silane
Office Paper
20 / 6

Technical Data

Power Supply
24 V DC
Temperature (operation)
-55°C - 75°C
Humidity
0 to 95 % r.h., non-condensing
Dimensions (H × W × D)
0.1x0.12x0.16 m
Weight
6.17 lb
Housing Material
Stainless steel SS 316 or Heavy duty copper free aluminum, red epoxy enamel finish
Degree of protection (IP class)
IP66/67

Approvals

ATEX
IECEx
UL
CSA
CE marking
GOST (EAC)
Performance approval
Shipping approval (DNV & MED)
FM

Compare with related ProductsShare

Get in touch with Dräger

Contact Us Image Safety Products

Draeger Safety UK Ltd.

Ullswater Close, Blyth Riverside Business Park
Blyth, Northumberland, NE24 4RG

+44 (0) 1670 352 891

Call us from Mon - Thurs 8:30am - 5pm
Fri 8:30am - 2pm

Draeger Marine and Offshore

Unit 2 Tern Pl, Bridge of Don
Aberdeen, AB23 8JX
+44 (0) 1224 701 569