Fast, reliable, safe: The right flame detection for your application
Quick Links
SpecificationsAccessoriesDownloadsContact us
Radiation
Measuring Principle
Horizontal 100°, Vertical 80°
Field of view
Typically 5 seconds
Response time
-60°C - 85°C
Temperature (operation)
Open full specifications
Highlights
The Dräger Flame 1350 combines UV and IR sensors to detect hydrocarbon-based fires. These powerful sensors and complex algorithms provide increased safety and fewer false alarms.
Fast and safe detection
The Dräger Flame 1350 combines a UV and an IR sensor to safely and reliably detect hydrocarbon-based fires. Due to its reliability and performance, it meets IEC 61508 safety integrity requirements according to SIL2, as well as the high performance re … More informationquirements of EN54-10 and FM3260. The flame detector also features HART® and RS-485 interfaces and has low power consumption.
Prevention of false alarms
With its two sensors, the Flame 1350 detects electromagnetic radiation in the short-wave UV range and in the IR spectrum. Frequency, intensity and duration of the measuring signals are analysed. An alarm is only triggered if the response criteria of … More informationboth sensors are met. In this way, the Flame 1350 avoids false alarms. In addition, the sensitive detection ensures that the detector does not falsely report fire from other zones.
Robust and durable
The housing is very robust and weatherproof. The window can be heated automatically to protect it from icing and fogging. This allows you to operate the Flame 1350 reliably even under extreme environmental conditions, e.g. in temperatures from -60 °C … More information to +85 °C.
Simple verification
The built-in self-test "Advanced Optical Verification" (AOV) automatically checks the electronics and optics of the Flame 1350. The three-colour LED on the front allows you to quickly recognise the device status. Green stands for normal operation, ye … More informationllow indicates a fault and red signals a fire alarm.
Key features
Wide coverage: Offers a maximum coverage of 100° horitontal by 80° vertical, and a maximum detection range of 39 meters.
All-weather availability: Equipped with a heated window to combat frost and fogging, ensuring yearround functionality.
Low maintena … More information
nce: Built-in self-test eliminates the need for external equpment, ensuring minimal maintenance throughout its lifetime.
Service - Repair & Maintenance
You trust our products for the safety of your employees and the continuity of your processes. Products work at their best when they are correctly and regularly maintained which protects the value of your investment, minimises downtime and supports the efficiency of your processes.
The weather shield for a flame detector is designed to protect the sensitive optics from rain, dust, snow, and direct sunlight. It ensures that the detector maintains a clear view of the monitored area without interference from harsh outdoor conditions.
Dräger FS-5000
Simulates presence of fire for testing Flame 5000
Designed for extreme offshore environmental conditions