Fast, reliable, safe: The right flame detection for your application
Quick Links
SpecificationsAccessoriesDownloadsContact us
Radiation
Measuring Principle
Horizontal 90°; Vertical 90
Field of view
Typically 4 seconds
Response time
−60°C - 85°C
Temperature (operation)
Open full specifications
Highlights
The Dräger Flame 1500 flame detector uses its triple IR sensor to detect hydrocarbon fires even at great distances. It offers you high reliability against false alarms.
Fast and reliable flame detection
The Dräger Flame 1500 is equipped with three infrared sensors. They enable it to detect hydrocarbon-based fires even at a great distance. This reliability allows it to meet IEC 61508 requirements for safety integrity according to SIL2. The flame dete … More informationctor also has a HART® interfaces via which it can be connected directly to the fire alarm system, for example. In addition, the Flame 1500 has a low power consumption.
Prevention of false alarms
The Flame 1500 measures infrared radiation in three different wavelengths and compares them with the reference value of CO2, which is produced during the combustion of hydrocarbons. In combination with the analysis of the flame's flickering, the comp … More informationlex algorithm identifies a fire and excludes sources of interference. In this way, the Flame 1500 reliably prevents false alarms caused by possible fault sources such as welding work or black body radiation.
Robust and resistant
The powder-coated housing made of stainless steel or aluminum is very robust and weatherproof. The viewing window is heated to protect against icing and fogging. This allows you to operate the Flame 1500 reliably under a wide range of environmental c … More informationonditions.
Simple check
The Optical Verification Test (OVT) automatically checks the electronics and optics of the Flame 1500 without affecting the field of view. The three-colour LED on the front lets you quickly see the status of the unit. Green stands for normal operatio … More informationn, yellow indicates a fault and red signals a fire alarm.
Key features
Fast reaction time: Less than five seconds for tested with a one-meter n-Heptane fire from 120 meters distance. Avoidance of false alarms: Using three infrared sensors and sophisticated algorithms. All-weather availability: Equipped with a heated win … More informationdow to combat frost and fogging, ensuring year round functionality
Specifications
Radiation
Measuring Principle
Horizontal 90°; Vertical 90
Field of view
Typically 4 seconds
Response time
−60°C - 85°C
Temperature (operation)
Key Facts
Measuring Principle
Radiation
Field of view
Horizontal 90°; Vertical 90
Response time
Typically 4 seconds
Cable entry
Dual M25 or ¾''NPT
Flameproof
yes
Increased Safety
no
SIL
yes SIL 2 (IEC 61508-1-3)
4-20 mA
yes
HART®
yes
RS-485
yes
Relay
yes
Fuel measuring range
n-Butane
50 m
Methane
50 m
Ethanol
42 m
n-Heptane
120 m
JP4
61 m
Diesel Fuel / JP5 / Kerosene
50 m
Propane
50 m
Ethylene glycol
24 m
Crude oil
50 m
Gasoline
57 m
Methanol
43 m
IPA (Isopropyl Alcohol)
45 m
LPG
50 m
Polypropylene Pellets
20 m
Acetone
57 m
Hexane
52 m
Technical Data
Power Supply
18 to 32 V DC (24 V DC nominal)
Temperature (operation)
−60°C - 85°C
Humidity
0 to 100 % r.h., non-condensing
Dimensions (H × W × D)
14,5x10 cm
Weight
4,5 Kg
Housing Material
Aluminium or stainless steel, powder-coated
IP class
IP66 / NEMA 4X
Approvals
ATEX
yes
IECEx
yes
UL
no
CSA
yes
CE marking
yes
GOST (EAC)
yes
Performance approval FM3260
yes
Performance approval (DNV Type Approval)
yes
Shipping approval (DNV Type Approval)
yes
FM
yes
See the whole Product System.
—
This product is part of a Dräger system solution. Combine it with the following system components.
The weather shield for a flame detector is designed to protect the sensitive optics from rain, dust, snow, and direct sunlight. It ensures that the detector maintains a clear view of the monitored area without interference from harsh outdoor conditions.